Zone Temperature Control Modes

The left electronic controller controls the aft cabin zone and provides backup control for the flight
deck. The right controller controls the forward cabin zone and provides primary control for the
flight deck. Failure of the primary flight deck temperature control will cause an automatic switch to
the back up control and will illuminate the CONT CAB amber ZONE TEMP light upon Master Caution
Recall. Failure of both the primary and standby controls will illuminate the lights automatically.
Failure of the forward or aft cabin temperature control will cause the associated trim air modulating
valve to close. The Temperature Selectors operate normally, but the Temperature Selector settings
of the two passenger cabin zones will be averaged. The amber ZONE TEMP light will illuminate
upon Master Caution Recall to indicate failure of the associated zone control.

Unbalanced Pack Temperature Control Mode

Any failure affecting the supply of trim air will cause the temperature control system to control both
packs independently. If flight deck trim air is lost, the left pack will provide conditioned air to the
flight deck at the selected temperature and the right pack will satisfy the demand of the passenger
zone which requires the most cooling. If a passenger cabin zone trim air, or all trim air is lost, the
forward and aft zone temperature demands will be averaged for control of the right pack. If any
individual zone is switched OFF, the Temperature Selector setting will be ignored by the
temperature control system.