Standby Pack Average Temperature

If all zone controls and primary pack controls fail, the standby pack
controls command the packs to produce air temperatures which will
satisfy the average temperature demand of the two cabin zones. The
trim air modulating valves will close. The flight deck zone
Temperature Selector will have no effect on the standby pack controls.

Fixed Cabin Temperature

If all Temperature Selectors are positioned OFF, the pack controls will
cause the left pack to maintain a fixed temperature of 75 degrees F
(24 degrees C) and the right pack to maintain 65 degrees F
(18 degrees C) as measured at the pack temperature sensor.